Wago - 2857-535

$565.70
Wago - 2857-535 is available to buy in increments of 1
Overview
T-TRANSDUCER UI
  • Technical data - Configuration - Configuration options:
    • WAGO Interface Configuration Software
    • WAGO Interface Configuration App
    • WAGO Configuration Display
  • Environmental requirements - Operating altitude (max.):2000m
  • Safety and protection - Note on insulation parameters:
    • The digital output (DO) is at the potential of the supply.
    • The service interface is located on the analog output potential.
    • The DIN-rail contact (functional ground) is capacitively coupled to the analog output.
  • Safety and protection - Insulation coordination (UL) - Insulation type (input/DIN-rail contact/relay output/supply):Reinforced insulation (safe isolation)
  • Technical data - Power supply - Power supply type:24 VDC
  • Technical data - Power supply - Nominal supply voltage US:DC 24 V
  • Technical data - Power supply - Supply voltage range:-60 ... +30 %
  • Safety and protection - Rated voltage:300V
  • Technical data - Output (relay) - Switching voltage (max.):AC 250 V
  • Safety and protection - Rated voltage of the measurement circuit connections per EN 61010-2-030:AC 300 V
  • Technical data - Output (relay) - Dielectric strength (open contact) (AC, 1 min):
    • 1kVrms
    • 1 kVrms
  • Connection data - Connection technology:Push-in CAGE CLAMP(R)
  • Connection data - WAGO connector:picoMAX(R) 5.0
  • Connection data - Solid conductor:0.2 ... 2.5 mm2 / 24 ... 12 AWG
  • Connection data - Fine-stranded conductor:0.2 ... 2.5 mm2 / 24 ... 12 AWG
  • Mechanical Data - Mounting type:DIN-35 rail
  • Technical data - Input - Input signal type:
    • RTD sensors
    • Potentiometer
    • Resistance
    • TC sensors
  • Technical data - Input (RTD sensors) - Sensor types (RTD):Pt10 ... Pt2000 (expandable)
  • Technical data - Input (RTD sensors) - Temperature measurement range (RTD):-200 ... 850°C
  • Technical data - Input (TC sensors) - Sensor types (TC):
    • Type J
    • Type K
    • Type E
    • Type R
    • Type N
    • Type S
    • Type T
    • Type B
    • Type C
  • Technical data - Input (TC sensors) - Temperature measurement range (TC):-210 ... 1200 °C (Type J); -200 ... 1372 °C (Type K); -200 ... 1000 °C (Type E); 250 ... 1768 °C (Type R); -200 ... 1300 °C (Type N); -50 ... 1664 °C (Type S); -200 ... 400 °C (Type T); 250 ... 1820 °C (Type B); 0 ... 2320 °C (Type C)
  • Technical data - Output (analog) - Output signal type:
    • Current
    • Voltage
  • Technical data - Output (analog) - Output signal (voltage):Â+/- 12 V
  • Technical data - Measurement error - Temperature coefficient:≤ 0.01 %/K
  • Technical data - Measurement error - Transmission error (typ.):≤ 0.1 % at full measurement span
  • Technical data - Measurement error - Transmission error for the set measurement range:≤ (100 K/set measurement range [K]) %
  • Technical data - Output (relay) - Number of changeover/switchover contacts:1
  • Physical data - Width:22.5 mm / 0.886 inches
  • Environmental requirements - Ambient temperature (operation):-40 ... +70 °C
  • Environmental requirements - Ambient temperature (storage):-40 ... +85 °C
  • Environmental requirements - Relative humidity:5 ... 95 % (non-condensing)
  • Technical data - Power supply - Current consumption at nominal supply voltage:≤ 70 mA (+ IDO)
  • Commercial data - GTIN:4055140000000
  • Commercial data - ETIM 8.0:EC002919
  • Commercial data - ETIM 7.0:EC002919
  • Commercial data - eClass 10.0:27-21-01-29
  • Commercial data - eClass 9.0:27-21-01-29
  • Commercial data - Customs tariff number:85437090300
  • sku_code:2857-535
  • Environmental Product Compliance - RoHS Compliance Status:Compliant,With Exemption
  • approvals_General approvals:UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 61010-2-201 - certificate E175199
  • Environmental Product Compliance - RoHS Exemption:
    • 6(c)
    • 7(a)
    • 7(c)-I
    • 7(c)-II
  • Standards and specifications - Standards/specifications:
    • EN 61010-1
    • EN 61373
    • EN 61010-1
    • EN 61373
  • Standards and specifications - Conformity marking:CE
  • Standards and specifications - EMC emission of interference:EN 61000-6-3; EN 61326-2-3
  • Standards and specifications - EMC immunity to interference:EN 61000-6-2; EN 61326-2-3
  • Safety and protection - Insulation coordination (UL) - Overvoltage category:II
  • Commercial data - Country of origin:DE
  • Environmental requirements - Pollution degree:2
  • Safety and protection - Insulation coordination (UL) - Pollution degree:2
  • ACCESSORIES_Markingaccessories:
    • 2009-110
    • 2009-115
    • 2009-141
    • 793-501
    • 793-502
    • 793-503
    • 793-504
    • 793-505
    • 793-506
    • 793-5501
    • 793-566
  • ACCESSORIES_Tools:210-720
  • ACCESSORIES_Assembling:
    • 249-116
    • 249-117
    • 249-197
  • ACCESSORIES_Check:735-500
  • ACCESSORIES_Jumper:
    • 281-482
    • 859-402
    • 859-402/000-005
    • 859-402/000-006
    • 859-402/000-029
  • ACCESSORIES_Clamps:857-979
  • ACCESSORIES_Communication:
    • 2857-900
    • 750-921
    • 750-923
    • 750-923/000-001
  • ACCESSORIES_PowerSupply:787-2852
  • ACCESSORIES_Relay_module:857-304
  • manufacturer_description:Temperature signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC
  • picture_filename_1:1024-8120132-DE.jpg
  • picture_zoom_filename_1:2000-8120132-DE.jpg
  • Material data - Weight:126.9g
  • Material data - Fire load:2.168MJ
  • picture_filename_2:1024-020000290000e777000100b6-DE.jpg
  • picture_zoom_filename_2:2000-020000290000e777000100b6-DE.jpg
  • Physical data - Height:110 mm / 4.331 inches
  • manufacturer_detailed_description:Short description:
    WAGO's RTD TC temperature signal conditioner for RTD sensors, potentiometers, resistors and thermocouples monitors and reports signals for up to two switching thresholds. The sensor and status information that is collected is also converted to a standard analog signal.
    Features:
    • A relay with changeover contact reacts to configured measurement range limits (on/off switching delay and threshold value switch function can be configured with up to two threshold values).
    • Configurable Pt factor
    • Adjustable software filter
    • Simulation of input/output response via interface configuration display
    • Input of customer-specific sensors via the interface configuration software
    • Safe 3-way isolation with 3 kV test voltage per EN 61010-1
    • Analog unipolar/bipolar signals (current/voltage) at output
    • Additional digital signal output for configured measurement range limits
    • Adjustable transfer characteristic
  • picture_filename_3:1024-020000290002953f000100b6-DE.jpg
  • picture_zoom_filename_3:2000-020000290002953f000100b6-DE.jpg
  • Physical data - Depth from upper-edge of DIN-rail:107 mm / 4.213 inches
  • Safety and protection - Protection type:IP20
  • Technical data - Input (resistors) - Input range (resistor):0 ... 10 kΩ
  • Technical data - Input (resistors) - Input range (potentiometer):0 ... 10 kΩ
  • Primary brand: Wago
  • Functions: Temperature signal transducer / conditioner
  • Design:
    • analog output
    • software configuration
  • Supply voltage (DC): 16.8-26.4Vdc (24Vdc nom.)
  • Connection type: Push-in CAGE CLAMP spring connections
  • Mounting mode: DIN-35 rail
  • Digital outputs: 1 x digital output (SPDT (Single Pole Double Throw) rly. contact type; 250Vac 6A)
  • Analog inputs: 1 x analog input (RTD Pt10 / Pt2000 / Thermocouples types J; K; E; R; N; S; T; B; C / Resistor; 0-10kΩ / Potentiometer; Resistor; 0-10kΩ; 2-wire / 3-wire / 4-wire)
  • Analog outputs: 1 x analog output (-24...+24mA / -12...+12Vdc)
  • Measurement accuracy:
    • ≤ 0.1% (transmission error)
    • ≤ 0.01%/K (temperature coefficient)
  • Dimensions: H110mm x W22.5mm x D107mm
  • Net Width (mm): 22.5mm
  • Ambient air temperature for operation: -40°C...+70°C
  • Ambient air temperature for storage: -40°C...+85°C
  • Humidity: 5-95% relative humidity (RH; non-condensing)
  • Current consumption: 70mA (24Vdc; at nominal load)
  • GTIN code: 4055140000000
  • ETIM code: EC002919
  • eClass code: 27-21-01-29
  • Customs Tariff Number: 85437090300
  • Order code / Manufacturer SKU: 2857-535
  • Manufacturer product status: Commercialized
  • Equivalent to: 2857535
  • EAN code: 4055140000000
  • Compliant with standard(s):
    • CE
    • EN 61010-1
    • EN 61373
    • EMC immunity to interference
    • - EN 61000-6-2
    • - EN 61326-2-3
    • EMC emission of interference
    • - EN 61000-6-3
    • - EN 61326-2-3
    • General approvals
    • - UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 61010-2-201 - certificate E175199
    • RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
  • Location of origin: Germany
  • Degree of pollution: 2
  • Cross-sells with:
    • 2009-110
    • 2009-115
    • 2009-141
    • 210-720
    • 249-116
    • 249-117
    • 249-197
    • 281-482
    • 2857-900
    • 735-500
    • 750-921
    • 750-923
    • 750-923/000-001
    • 787-2852
    • 793-501
    • 793-502
    • 793-503
    • 793-504
    • 793-505
    • 793-506
    • 793-5501
    • 793-566
    • 857-304
    • 857-979
    • 859-402
    • 859-402/000-005
    • 859-402/000-006
    • 859-402/000-029
  • Level 1 category: Electrical components
  • Level 2 category: Metering devices
  • Level 3 category: Measurement sensors
  • Level 4 category: Transducers
  • Product title: Temperature signal transducer / conditioner - analog output - Wago (JUMPFLEX series)
More Information
Main function Transducer (Digital)
Product series / family name 2857 series
Sub-range name JUMPFLEX series
Supply voltage (DC) 24Vdc
Connection type (electrical) Terminals (Spring)
Mounting mode DIN rail
Digital outputs type AC, Relay (type 1a1b)
Analog inputs type Thermocouple, Thermocouple type C
Analog outputs type Current, Voltage
Degree of protection IP20
Type - Option Standard (No options)
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
Copyright © 2023 US Automation Controls LLC, All Rights Reserved.