- Environmental requirements - Operating altitude:0 ... 2000 m / 0 ... 6562 ft
- Technical data - Indicators:LED (A, E) green: Function HART 1, HART 2; LED (B, F) red: Error HART 1, HART 2
- Technical data - Number of outgoing power jumper contacts:2
- Technical data - Number of incoming power jumper contacts:2
- Technical data - Data width:2 x 2-byte data; 2 x 2-byte data + 2n x 4-byte data (n = number of dynamic variables); 2 x 2-byte data + 6-byte mailbox
- Technical data - Intrinsic safety Ex i:Yes
- Technical data - Supply voltage (system):5 VDC; via data contacts
- Technical data - Supply voltage (field):24 VDC; (Ex i power supply: Uo = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Technical data - Current carrying capacity (power jumper contacts):1A
- Technical data - Total number of channels (module):2
- Technical data - Isolation:300 VAC system/supply
- Connection data - Connection type 1:Inputs/outputs
- Connection data - Solid conductor:0.08 ... 2.5 mm2 / 28 ... 14 AWG
- Connection data - Fine-stranded conductor:0.08 ... 2.5 mm2 / 28 ... 14 AWG
- Technical data - Diagnostics:Wire break; short circuit; measurement range overflow; measurement range underflow according to NAMUR recommendation 43
- Technical data - Overvoltage protection:30 V, reverse polarity protected
- Mechanical data - Mounting type:DIN-35 rail
- Environmental requirements - Mounting position:horizontal (standing/lying); vertical
- Technical data - Sensor connection:2 x (2-wire)
- Technical data - Signal type:Current
- Technical data - Resolution [bit]:12bits
- Technical data - Signal characteristics:Single-ended
- Technical data - Signal type (current):4 ... 20 mADC
- Technical data - Input filter:parameterizable
- Technical data - Measurement error, deviation (max.) from the upper-range value:0.002
- Technical data - Measurement error (reference temperature):25°C
- Technical data - Temperature error (max.) of the upper-range value:0.01%/K
- Physical data - Width:24 mm / 0.945 inches
- Material data - Housing material:Polycarbonate; polyamide 6.6
- Environmental requirements - Ambient temperature (operation):0 ... +55 °C
- Environmental requirements - Ambient temperature (storage):-25 ... +85 °C
- Environmental requirements - Relative humidity (without condensation):0.95
- Environmental requirements - Permissible H2S contaminant concentration at a relative humidity
75 %:10ppm - Environmental requirements - Permissible SO2 contaminant concentration at a relative humidity
75 %:25ppm - Environmental requirements - Shock resistance:15g per IEC 60068-2-27
- Environmental requirements - Vibration resistance:4g per IEC 60068-2-6
- Technical data - Conversion time (typ.):10ms
- Technical data - Current consumption (5 V system supply):25mA
- Technical data - Current consumption, field supply (module with no external load):26mA
- Technical data - Power consumption Pmax.:1.60 W (with slaves (20 mA))
- Commercial data - ETIM 8.0:
- EC001596
- Commercial data - ETIM 7.0:
- EC001596
- Commercial data - eClass 10.0:27-24-26-01
- Commercial data - eClass 9.0:
- 27-24-26-01
- Commercial data - Customs tariff number:85389099990
- Technical data - Power loss Pl:0.62 W (without slaves)
- sku_code:750-484/000-001
- Environmental Product Compliance - RoHS Compliance Status:Compliant,With Exemption
- approvals_General approvals:UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199 Sec.1
- approvals_Declarations of conformity and manufacturer's declarations:EU-Declaration of Conformity - WAGO GmbH & Co. KG - certificate -
- Environmental Product Compliance - RoHS Exemption:
- 6(c)
- 7(a)
- 7(c)-I
- 7(c)-II
- approvals_Approvals for hazardous areas:
- ATEX - TUEV Nord Cert GmbH - EN 60079 - certificate TUEV_12_ATEX_106032X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)
- CCC - CNEX - CNCA-C23-01 - certificate 2020312310000211 (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)
- EAC - Brjansker Zertifizierungsstelle - TP TC 012/2011 - certificate EAC RU C-DE.AM02.B.00163/19 ([ExiaMa]I X / 2Ex e[iaGa]IIC T4Gc X / [ExiaDa]IIIC X)
- INMETRO - TUV Rheinland do Brasil Ltda. - certificate TUV_14.1911_X
- TUEV Nord - TUEV Nord Cert GmbH - IEC 60079 - certificate IECEx TUN 12.0039X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)
- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726 Sec.1
- Environmental requirements - Exposure to pollutants:per IEC 60068-2-42 and IEC 60068-2-43
- Material data - Conformity marking:CE
- Explosion protection - Ex standard:EN IEC 60079-0, -7, -11
- Explosion protection - Marking:ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I
- Commercial data - Country of origin:DE
- Environmental requirements - Pollution degree:2 per IEC 61131-2
- manufacturer_description:2-channel analog input; 4 ... 20 mA HART; NAMUR NE 43; Intrinsically safe
- picture_filename_1:1024-0200002a00002adc000100b6-DE.jpg
- picture_zoom_filename_1:2000-0200002a00002adc000100b6-DE.jpg
- Material data - Weight:91.9g
- Material data - Fire load:2.034MJ
- picture_filename_2:1024-0200002a0000017d000100b6-EN.jpg
- picture_zoom_filename_2:2000-0200002a0000017d000100b6-EN.jpg
- Physical data - Height:100 mm / 3.937 inches
- manufacturer_detailed_description:
This analog input module connects two field-side signal conditioners equipped with a HART interface that are to be used in hazardous areas of Zone 0+1.
The module supplies signal conditioners, reads process values via analog interface, and enables HART communication for configuring and importing dynamic variables.
The WAGO I/O System 750 must be installed either in Zone 2 or in a non-hazardous area.
The 24 V supply is supplied to the field contacts (HART +) from the power jumper contacts via multipliers. The shield directly connects to the DIN-rail.
The measurement input is equipped with current limitation, which limits the current to 25 mA. This module powers 2-wire signal conditioners without dedicated power supply.
Up to 4 HART dynamic variables (PV, SV, TV, QV) per channel can be mapped in the cyclic process image of the coupler or controller (parameterizable). For HART communication with connected intelligent HART field devices, the HART protocol can be mapped in the cyclic process image of the coupler or controller (parameterizable).
FDT/DTM device drivers are available for select (programmable) couplers, allowing HART tool routing to the connected HART device.
- Physical data - Depth:67.8 mm / 2.669 inches
- picture_filename_3:1024-0200002c0000ed5c000200b6-EN.jpg
- picture_zoom_filename_3:2000-0200002c0000ed5c000200b6-EN.jpg
- picture_filename_4:1024-0200002600035735000100b6-DE.jpg
- picture_zoom_filename_4:2000-0200002600035735000100b6-DE.jpg
- Physical data - Depth from upper-edge of DIN-rail:60.6 mm / 2.386 inches
- Environmental requirements - Protection type:IP20
- Environmental requirements - EMC emission of interference:per EN 61000-6-3, marine applications
- Environmental requirements - EMC immunity to interference:per EN 61000-6-2, marine applications
- Technical data - Number of analog inputs:2
- Primary brand: Wago
- Functions: Intrinsically-safe analog input slice module
- Supply voltage (DC):
- 5Vdc (supplied by system)
- 24Vdc fixed suppl. to field sensing devices
- Connection type: Push-in spring CAGE CLAMP connections
- Protection functions:
- wire-break protection
- overvoltage protection
- reverse polarity protection
- Mounting mode: DIN-35 rail
- Analog inputs: 2 x analog inputs (4-20mA; Single-ended; 12-bits / 10ms conversion / HART / NAMUR; 2-wire)
- Measurement accuracy:
- +-0.2% (measuring error)
- +-0.01% (temperature error)
- Dimensions: H100mm x W24mm x D67.8mm
- Net Width (mm): 24mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -25°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance:
- Vibration resistance according to EN 60068-2-6 -- 4g
- Shock resistance according to EN 60068-2-27 --15g
- Current consumption:
- 25mA (5Vdc; system supply)
- 26mA (field supply; no external load)
- ETIM code: EC001596
- eClass code: 27-24-26-01
- Customs Tariff Number: 85389099990
- Power dissipation/losses: 0.62W
- Order code / Manufacturer SKU: 750-484/000-001
- Manufacturer product status: Commercialized
- Equivalent to: 750484000000
- Compliant with standard(s):
- EMC immunity to interference
- - EN 61000-6-2
- - marine applications
- EMC emission of interference
- - EN 61000-6-3
- - marine applications
- General approvals
- - UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199 Sec.1
- Declarations of conformity and manufacturer's declarations
- - EU-Declaration of Conformity - WAGO GmbH & Co. KG
- Approvals for hazardous areas
- - ATEX - TUV Nord Cert GmbH - EN 60079 - certificate TUV_12_ATEX_106032X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)
- - CCC - CNEX - CNCA-C23-01 - certificate 2020312310000211 (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)
- - EAC - Brjansker Zertifizierungsstelle - TP TC 012/2011 - certificate EAC RU C-DE.AM02.B.00163/19 ([ExiaMa]I X / 2Ex e[iaGa]IIC T4Gc X / [ExiaDa]IIIC X)
- - INMETRO - TUV Rheinland do Brasil Ltda. - certificate TUV_14.1911_X
- - TUV Nord - TUV Nord Cert GmbH - IEC 60079 - certificate IECEx TUN 12.0039X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)
- - UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726 Sec.1
- RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Programmable Logic Controllers & components
- Level 3 category: I-O Units
- Product title: Intrinsically-safe analog input slice module - Wago
Main function | I/O unit |
---|---|
Product series / family name | 750 series |
Connection type (electrical) | Terminals (Spring) |
Communication protocol | HART |
Mounting mode | DIN rail |
Digital inputs quantity | no digital inputs |
Digital outputs quantity | no digital outputs |
Analog inputs quantity | 2 |
Analog inputs type | Current |
Analog input resolution | 12-bit |
Analog outputs quantity | no analog outputs |
Degree of protection | IP20 |
Type - Installation | in cabinet |